< previous page page_181 next page >

Page 181
0181-01.gif
Figure 13.3
A comparison between the multiple ball efficiencies obtained by
the Mark 0, Mark III and 'field' Mark III WCs
performed better than the original (Mark 0) Twyfords WC flushing with 9 litres. Figure 13.4 presents the results of the liquid contamination test, with a lower residual concentration for the Mark III WCs at 3 litres than the Mark 0 WC at 9 litres. The Mark III WCs only required 2 litres to pass the BS5503 paper and ball tests, but required 3.5 litres to pass the BS5503 sawdust test.
Results from the solid transportation tests are shown in Figure 13.5, presented as solid velocity along the drain, set at a gradient G at distance L from the WC drain connection, plotted as Ö(L/G), providing a linear characteristic (Swaffield and Wakelin, 1976). Figure 13.5 indicates that a flush volume of 3 litres should only be adopted for drain lengths up to 11.25 m at a gradient of 1 in 80 prior to inflow connection from other sanitary appliances. Most on-site sewage disposal or storage systems would meet this restriction. For drains connected to a main sewer, a minimum flush volume of 4 litres was recommended to achieve similar solid transportation performance to the Mark 0 WC flushed with 9 litres. These flush volumes were adopted for the site trials.
These results confirmed Uujamhan's (1981) functional relationship (equation 13.1 and Figure 13.2) for solid and fluid contamination removal. From Figure 13.2 the value of the dimensionless

 
< previous page page_181 next page >